Heavy Duty Type Digital Pressure Sensors

GP-M series

Catalogues View Catalogue

Specs Heavy Duty Type Digital Pressure Sensors GP-M series

Model

GP-M001T

GP-M010T

GP-M025T

GP-M100T

GP-M250T

GP-M400T

Image

Rated pressure

–100 to +100 kPa

–0.1 to +1 MPa

–0.1 to +2.5 MPa

0 to +10 MPa

0 to +25 MPa

0 to +40 MPa

Possible display range

–120.0 to +120.0 kPa

–0.210 to +1.110 MPa

–0.360 to +2.760 MPa

–1.00 to +11.00 MPa

–2.50 to +27.50 MPa

–4.00 to +44.00 MPa

Allowable pressure

400 kPa

4 MPa

10 MPa

30 MPa

50 MPa

Zero-cut pressure value

±0.5% of F.S.

Burst pressure

1.5 MPa

15 MPa

35 MPa

100 MPa

Display resolution

0.1 kPa

0.001 MPa

0.01 MPa

Fluid type

Gas or liquid that will not corrode the fluid contact part

Liquid that will not corrode the fluid contact part

Type of pressure

Gauge pressure

Precision

±1.0% of F.S. or less*1

Repeatability

±0.3% of F.S. or less*2

Temperature characteristics

±0.6% of F.S. / 10°C

Connection diameter

G3/4 (Changes to R1/8 male, R1/4 male, R3/8 male, G1/4 female, NPT1/8 male, and NPT1/4 male with available adapters.)

Box rotation angle

Maximum 330°

Medium temperature

–20 to +100°C (no freezing/condensation)*3*4

Power supply voltage

10 to 30 VDC, Ripple (P-P): 10% max., Class 2 or LPS

Current consumption

60 mA or less (when 24 V: 30 mA or less; when 12 V: 50 mA or less. Excluding output)*5

Possible display range (temperature)

–32 to +112°C

Display method

4 column digital LED white/Vertical inversion of display is possible

Display resolution (temperature)

0.1°C

Liquid contact temperature measurement accuracy

±3.5°C (at an ambient temperature of 25°C)*6

Indicators

Status indicator (orange, green, red, blue), output indicator 1 (orange), output indicator 2 (orange), temperature indicator (white), communication indicator (green)

Pressure hysteresis

During hysteresis mode: variable (Hysteresis is the difference between the upper setting value and the lower setting value)
During window mode: fixed (0.5% of F.S.)

Pressure responsiveness

Control output

Selectable from 3 to 5000 ms

Analogue output

As above +2 ms (90% response)

Output

Output 1 control output

NPN/PNP open collector (Selectable) 30 V or less,
Max. 100 mA Residual voltage for the Main Unit is 1 V or less, N.O./N.C. selectable

Output 2
replacement type

Control output

Analogue output

Pressure analogue output/temperature analogue output (selectable), 4–20 mA; maximum load resistance 260 Ω

Network compatibility

IO-Link*7

Environmental resistance

Enclosure rating

IP67

Ambient temperature

–20 to +80°C (no freezing or condensation)*4

Relative humidity

35 to 85% RH (no condensation)*4

Vibration resistance

IEC60068-2-6 20 G (10 to 2000 Hz In each direction of X, Y, Z for 2 hours)

Shock resistance

IEC60068-2-27 50 G (11 ms In each direction X, Y, Z 3 times)

Material
properties

Port/diaphragm

Pressure port: SUSXM7/Diaphragm pressure port: Al2O3/O-Ring: FKM

Other parts

Housing metal portion: SUS304, SUS303; Housing plastic portion: PPSU; Air hole*8: PTFE, nickel-plated brass.

Applicable cable

M12 connector 4 pin

Weight

Approx. 150 g

*1 This is the value when considering linearity + hysteresis + repeatability in a stable environment of 23°C.
*2 The repeatability, based on consistent conditions, is the difference in the detection points at the time of fluctuations in the repetition.
*3 When the temperature of the piping exceeds 80°C, do not connect the cable.
*4 Condensation may cause measurement failure or breakage. To prevent condensation, take the following measures:
• Make sure that the ambient temperature is the same or lower than the fluid temperature.
• Use A/C for dehumidification.
• Keep the sensor 30 cm or more from the cooling pipe using connective piping.
*5 Consumption current including output is 0.3 A and under.
*6 This is the value when the measured fluid is water and a KEYENCE adapter is used.
*7 IO-Link specification v1.1/COM2 (38.4 kbps) is supported.
*8 Only GP-M001T/M010T/M025T

Back to top

Model

GP-M001

GP-M010

GP-M025

GP-M100

GP-M250

GP-M400

Image

Rated pressure

-100 to +100 kPa
(-1 to +1 bar)

-0.1 to +1 MPa
(-1 to +10 bar)

-0.1 to +2.5 MPa
(-1 to +25 bar)

0 to +10 MPa
(0 to +100 bar)

0 to +25 MPa
(0 to +250 bar)

0 to +40 MPa
(0 to +400 bar)

Possible display range

-120.0 to +120.0 kPa
(-1.200 to +1.200 bar)

-0.210 to +1.110 MPa
(-2.10 to +11.10 bar)

-0.360 to +2.760 MPa
(-3.60 to +27.60 bar)

-1.00 to +11.00 MPa
(-10.0 to +110.0 bar)

-2.50 to +27.50 MPa
(-25.0 to +275.0 bar)

-4.00 to +44.00 MPa
(-40.0 to +440.0 bar)

Zero-cut pressure value

±0.5% of F.S.

Burst pressure

1.5 MPa (15 bar)

15 MPa (150 bar)

35 MPa (350 bar)

100 MPa (1000 bar)

Display resolution

0.1 kPa (0.001 bar)

0.001 MPa (0.01 bar)

0.01 MPa (0.1 bar)

Fluid type

Gas or liquid that will not corrode the liquid contact part

Liquid that will not corrode the liquid contact part

Type of pressure

Gage pressure

Precision

±1.0% of F.S. or less*1

Repeatability

±0.3% of F.S. or less*2

Temperature characteristics

±0.6% of F.S./10°C

Connection diameter

G3/4 (Changes to the R male 1/8, R male 1/4, R male 3/8, G female 1/4, NPT male 1/8, and NPT male 1/4 option adapters are available.)

Box rotation angle

Maximum 330°

Medium temperature

-20 to +100°C (no freezing/condensation)*3

Power supply voltage

10-30 VDC, Ripple (P-P): 10% max, Class 2 or LPS

Current consumption

50 mA or less (when 24 V: 32 mA or less, when 12 V: 48 mA or less. Not including load)*4

Display method

4 column, digital LED, red/Vertical inversion display possible

Operation display light

Operation indicator (output 1) (orange), Operation indicator (output 2) (orange)

Hysteresis

During hysteresis mode: variable (Difference between switch-on point and switch-off point is hysteresis)
During window mode: fixed (0.5% of F.S.)

Response

Control output

Selectable from 3 to 5000 ms

Analogue output

As above + 2 ms (90% response)

Output

Output 1 control output

NPN/PNP open collector (Selectable), Max. 250 mA (30 V max)
Main unit residual voltage 1 V max, N.O./N.C. selectable

Output 2
replacement type

Control output

Analogue output

4-20 mA, maximum load resistance 500 Ω (When the electric voltage is more than 20 V)*5

Environmental resistance

Enclosure rating

IP67

Pressure resistance

400 kPa (4 bar)

4 MPa (40 bar)

10 MPa (100 bar)

30 MPa (300 bar)

50 MPa (500 bar)

Ambient temperature

-20 to +80 °C (No freezing and no condensation)

Relative humidity

35 to 85 % RH (No condensation)

Vibration resistance

IEC60068-2-6 20 G (10 to 2000 Hz, 2 hours each in the X, Y, and Z axes)

Shock resistance

IEC60068-2-27 50G (11 ms, 3 times for each of X, Y and Z direction)

Material
properties

Port/diaphragm

Pressure port: SUSXM7, Diaphragm pressure port: Al2O3 (Alumina), O ring: FKM

Other parts

Housing metal portion: SUS304, SUS303, Housing plastic portion: PPSU, Air hole: PTFE, nickel-plated brass.

Housing metal portion: SUS304, SUS303, Housing plastic portion: PPSU

Applicable cable

M12 connector 4 pin

Weight

Approx. 150 g

*1 This is the value when considering linearity + hysterisis + repeatability in a stable environment of 23°C.
*2 The repeatability, based on consistent conditions, is the difference in the detection points at the time of fluctuations in the repetition.
*3 When the temperature of the piping exceeds 80°C, do not connect the cable.
*4 Consumption current including output is 0.6 A and under.
*5 The maximum load resistance R will be the values below in response to the electric voltage E. When 10-23V: R = {38 x (E-10) + 128} Ω When 23-30V: R = 622 Ω

Back to top