Analogue Sensor Controller
RD series
Contact Us: +32 (0) 15 281 222 Enquiry form
Main Unit RD-50EW
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model  | RD-50EW  | |||
Measurement function  | DC voltage measurement, DC current measurement  | |||
A/D converting system  | Successive comparison  | |||
Measurement range  | ±5 VDC, ±10 VDC, 4 to 20 mA DC (selectable)  | |||
Display range  | -19999 to +39999  | |||
Measurement accuracy  | ±0.03 % of F.S. (at ±5 VDC range), ±0.03 % of F.S. (at ±10 VDC range)  | |||
Input  | Impedance  | 1 MΩ (for voltage input), 350 Ω (for current input)  | ||
System  | Single-ended  | |||
Number of inputs  | 2  | |||
Sampling rate  | 2,000 times/second  | |||
Display speed  | 20 times/second  | |||
Display power  | 7-segment 3-colour LED (character height: 15.24 mm)  | |||
Over-range alarm  | FFFF is displayed  | |||
Control input  | Synchronous, Hold-reset, Auto-zero, External setting,  | |||
Control input  | Timing input  | |||
Hold reset input  | ||||
Auto-zero input  | ||||
External setting input  | ||||
Controloutput  | Setting method  | 4 steps x 8 programmable setups (selectable)*1  | ||
Signal  | 5 x NPN (HH, HI, GO, LO, LL): 100 mA max. (40 V max.)*1  | |||
Response time  | 1 ms (when average number 1)*1  | |||
OFF-delay time  | 60 ms (ON/OFF selectable)*1  | |||
Analogue output voltage  | Output voltage  | ±10 VDC  | ||
Impedance  | 100 Ω  | |||
Response time  | 1 ms (when average number 1)*2  | |||
Interface  | Control input by NPN open-collector ornon-voltage contact signal  | |||
Major functions  | MDL, digital fi lter, auto-zero, offset, input, data processing (10 modes),  | |||
Rating  | Power voltage  | 24 VDC ±10 %, Ripple (P-P) 10 % or less  | ||
Current consumption  | 270 mA or less  | |||
Environmental resistance  | Ambient temperature  | 0 to +50 °C  | ||
Relative humidity  | 35 to 85 % RH (No condensation)  | |||
Vibration resistance  | 10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z directions  | |||
Weight  | Approx. 700 g (excluding fi ttings)  | |||
*1 NPN output can easily be converted to PNP output by connecting the optional OP-5148 PNP output converter.  | ||||