Air Efficiency Module
MP-F series
Energy Monitor Main Unit MP-FEA1
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model  | MP-FEA1  | |||
Measurement specifications  | Phase wire system  | 1-phase 2-wire, 1-phase 3-wire, 3-phase 3-wire, 3-phase 4-wire (switchable)  | ||
No. of measurement circuits  | 1 circuit (maximum of 2 circuits in a 1-phase 2-wire configuration *1)  | |||
Input specifications  | Primary side rated current (In)  | Dedicated MP-FEC100 CT: 100 A, or general-purpose CT (secondary side rated input current 1 A) *2  | ||
Overcurrent withstand capability  | 1.2 times the primary side rated current (can be continuous), 10 times the primary side rated current (1 sec or less)  | |||
Rated input voltage  | 1-phase 2-wire  | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 VAC to 277 VAC (L-N)  | ||
1-phase 3-wire  | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 VAC to 240 VAC (L-N), 200 VAC to 480 VAC (L-L)  | |||
3-phase 3-wire  | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 173 VAC to 480 VAC (L-L)  | |||
3-phase 4-wire  | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 100 to 277 VAC (L-N), 173 to 480 VAC (L-L)  | |||
Maximum allowable earth voltage  | When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: 480 VAC to earth  | |||
Input voltage fluctuation range constant  | -15% to +15% of rated input voltage  | |||
Rated input frequency  | 50/60 Hz  | |||
Displayable range  | Voltage  | Display resolution: 0.1 [V]  | ||
Current  | Display resolution: 0.001 [A]  | |||
Active power/Reactive power/Apparent power  | -8942.400 to +8942.400 [kW/kvar/kVA], Display resolution: 0.001 [kW/kvar/kVA]  | |||
Active energy/Reactive energy/Apparent energy  | 0.000 to 999999.999 [kWh/kvarh/kVAh], Display resolution: 0.001 [kWh/kvarh/kVAh]  | |||
Power factor (PF)  | -1.00 to 1.00, Display resolution: 0.01  | |||
Frequency  | 0.0 to 90.0 [Hz], Display resolution: 0.1 [Hz]  | |||
Measurement accuracy  | Voltage  | ±0.5% of RD (within rated input voltage) *3  | ||
Current  | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In < 5%) *2 *3  | |||
Active energy  | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: Complies with IEC62053-22 §7.9 table 3 class 0.5 *2 *3  | |||
Reactive energy  | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: Complies with IEC62053-23 §7.9 table 3 class 2 *2 *3  | |||
Apparent energy  | ・When using MP-FEC100/MP-FEC250/MP-FEC600 or general-purpose CT: ±0.5% of RD (5% ≤ In ≤ 120%), ±1.0% of RD (1% ≤ In < 5%) *2 *3 *4  | |||
Effects of ambient temperature  | ±0.03%/K *3 *5  | |||
Effects of harmonics  | ±0.5% of RD *3 *6  | |||
Power factor (PF)  | ±0.01 *3  | |||
Frequency  | ±0.1 [Hz] *3  | |||
Current consumption  | 36 mA  | |||
Withstand voltage  | Between all terminals and case: 2500 VAC for 1 minute  | |||
Insulation resistance  | Between all terminals and case: at least 20 MΩ min (500 VDC), Between voltage measurement terminals  | |||
Environmental resistance  | Ambient temperature  | -5 to +55°C (no freezing)  | ||
Relative humidity  | 35 to 85% RH (no condensation)  | |||
Measurement category  | ll  | |||
Usage altitude  | 2500 m or less  | |||
Pollution degree  | 2  | |||
Installation method  | DIN rail  | |||
Vibration resistance  | 10 to 500 Hz; Power Spectral Density: 0.033 G2/Hz for X, Y and Z directions  | |||
Shock resistance  | 150 m/s2, 2 times each for X, Y, and Z directions  | |||
Material  | Polycarbonate  | |||
Weight  | Approx. 110 g  | |||
*1 When measuring two circuits, use the same voltage and phase for the two circuits to be measured. Also, use CT of the same model.  | ||||